Reference
Ethernet Cable Standards
CAT3–CAT8 specs, speeds & distances, shielding types, RJ-45 pinouts, and broadcast wiring standards
| Category | Max Speed | Bandwidth | Max Distance | Shielding | Status | Notes / Best For |
|---|---|---|---|---|---|---|
| Cat3 | 10 Mbps | 16 MHz | 100 m (328 ft) | UTP only | Legacy | 10BASE-T, POTS voice/phone wiring. Still found in older buildings. |
| Cat5 | 100 Mbps | 100 MHz | 100 m (328 ft) | UTP / STP | Obsolete | Fast Ethernet only. Do not use for new installs — superseded by Cat5e. |
| Cat5e | 1 Gbps | 100 MHz | 100 m (328 ft) | UTP / STP | Common | Most common in existing installs. StudioHub/AngryAudio requires STP variant. |
| Cat6 | 1 Gbps / 10 Gbps | 250 MHz | 100 m @ 1G, 55 m @ 10G | UTP / STP | Current | Good all-purpose choice. 10G limited to 55 m. Spline reduces crosstalk. |
| Cat6A | 10 Gbps | 500 MHz | 100 m (328 ft) | UTP / STP | Recommended | Best for new installs. Full 10G at 100 m. Preferred for data centers & broadcast. |
| Cat7 | 10 Gbps | 600 MHz | 100 m (328 ft) | S/FTP only | Non-Std | Not an IEEE/TIA standard. Uses proprietary GG45 or TERA connectors. Avoid. |
| Cat7A | 10 Gbps | 1000 MHz | 100 m (328 ft) | S/FTP only | Rare | Rarely deployed. Same connector caveats as Cat7. Not widely supported. |
| Cat8.1 | 25–40 Gbps | 2000 MHz | 30 m (100 ft) | S/FTP only | Data Center | Switch-to-server in data centers only. Standard RJ-45 connectors (Cat8.1). |
Recommended by Use Case
ISO 11801 Shielding Notation
The naming convention reads as Overall Shield / Per-Pair Shield. Letters: U = Unshielded, F = Foil, S = Braided Screen, TP = Twisted Pair.
Example: S/FTP = Braided braid overall shield + Foil on each individual pair — highest protection class.
| Code | Common Name | Overall Shield | Per-Pair Shield | Typical Cat | Use Case |
|---|---|---|---|---|---|
| U/UTP | Unshielded Twisted Pair | None | None | Cat3–Cat6A | Lowest cost, easiest to install. Sufficient for most office/home networks. Most common. |
| F/UTP | Foiled Twisted Pair (FTP) | Foil | None | Cat5e–Cat6A | Light overall shield blocks external EMI. Good for moderate interference environments. |
| S/UTP | Screened UTP | Braid | None | Cat6–Cat6A | Braid provides better drain of EMI than foil. Slightly bulkier cable. |
| SF/UTP | Screened Foil UTP | Braid + Foil | None | Cat6A | Highest overall shielding without per-pair shields. Data center & industrial use. |
| U/FTP | Unshielded, Foiled Pairs | None | Foil per pair | Cat6A | No outer shield but each pair wrapped. Reduces ANEXT/alien crosstalk in Cat6A. |
| F/FTP | Foiled overall, Foiled Pairs | Foil | Foil per pair | Cat6A–Cat7A | High-performance. Eliminates inter-pair and external interference. StudioHub compatible. |
| S/FTP | Screened, Foiled Pairs | Braid | Foil per pair | Cat6A–Cat8 | Premium shielding. Required for Cat7/7A/8. Ideal for broadcast & AV over IP. |
Use Unshielded (UTP) When…
- Standard office or home environment
- No nearby high-EMI sources (motors, UPS, fluorescents)
- Budget and installation ease are priorities
- Running normal IT data networking (not audio)
- Existing infrastructure is UTP — matching is simpler
Use Shielded (STP/FTP) When…
- Always for StudioHub/AngryAudio broadcast audio wiring
- Running cable near power cables, UPS, AC units, or transmitters
- Industrial environments with heavy EMI
- Data center high-density runs (Cat6A S/FTP, Cat8)
- Outdoor or plenum environments with external interference
- AES50 digital audio (Midas, Behringer, DiGiCo)
Cable Construction Comparison
T568B — Most Common
| Pin | Color | Function |
|---|---|---|
| 1 | White/Orange | TX+ |
| 2 | Orange | TX− |
| 3 | White/Green | RX+ |
| 4 | Blue | — |
| 5 | White/Blue | — |
| 6 | Green | RX− |
| 7 | White/Brown | — |
| 8 | Brown | — |
T568A
| Pin | Color | Function |
|---|---|---|
| 1 | White/Green | TX+ |
| 2 | Green | TX− |
| 3 | White/Orange | RX+ |
| 4 | Blue | — |
| 5 | White/Blue | — |
| 6 | Orange | RX− |
| 7 | White/Brown | — |
| 8 | Brown | — |
Cable Types
| Type | Wiring | Use Case |
|---|---|---|
| Straight-through | T568B ↔ T568B (both ends same) | PC to Switch, Router to Switch |
| Crossover | T568A ↔ T568B (different ends) | Switch to Switch, PC to PC, Router to Router |
| Rollover / Console | Pin 1↔8, 2↔7, 3↔6, 4↔5 | PC serial to Cisco console port (RJ45) |
T568A vs T568B — When to Use Each
TIA/EIA-568 Structured Cabling Best Practices
TIA-568 is the North American standard governing commercial building telecommunications cabling — the spec your IT infrastructure should follow.
Installation Standards
- Use T568B for all terminations (consistent)
- Horizontal runs: solid-core cable only
- Patch cables: stranded for flexibility
- Max channel: 100 m (90 m run + 10 m patch)
- Untwist no more than 13 mm (½ in) at termination
- No kinks, sharp bends (< 4× cable diameter bend radius)
- Use Cat6A for all new installs targeting 10G
- Label both ends of every run
EMI & Separation Rules
- Min 6 in (150 mm) separation from power cables
- Min 12 in (300 mm) near high-voltage or fluorescents
- Cross power cables at 90° when unavoidable
- Use shielded cable near motors, UPS, transmitters
- Do not run data in same conduit as power
- Bond cable shields to ground at one end (rack/panel side)
- Use shielded patch panels in shielded installations
Category Recommendation Guide
| Application | Minimum | Recommended | Reasoning |
|---|---|---|---|
| Standard office (1 Gbps) | Cat5e UTP | Cat6 UTP | Cost-effective; handles 1G everywhere |
| Modern office (multi-gig) | Cat6 UTP | Cat6A UTP | Multi-gig switches becoming standard |
| New construction | Cat6A UTP | Cat6A S/FTP | Future-proof; no need to re-cable for 10G |
| Data center (server access) | Cat6A | Cat6A or Cat8.1 | Full 10G at 100 m; Cat8 for 25/40G short runs |
| Broadcast facility | Cat5e STP | Cat6A S/FTP | EMI immunity from transmitters, high-power audio gear |
| AV over IP / Dante | Cat6 UTP | Cat6A UTP | Low latency; QoS switch required (IEEE 802.1Q/p) |
| IP intercoms / VoIP | Cat5e UTP | Cat6 UTP | Low bandwidth but reliability matters |
| PoE devices (cameras, APs) | Cat5e | Cat6A | Higher gauge wire handles PoE heat better |
StudioHub / AngryAudio Wiring Standard
StudioHub (now Angry Audio) is the de facto broadcast audio wiring standard for radio and television facilities. It uses shielded Cat5e/Cat6 STP cable and standard RJ-45 connectors to carry balanced stereo audio and AES/EBU digital audio throughout a facility using a T568B pinout. Compatible with Axia/Telos Alliance, Wheatstone, and all StudioHub-equipped gear.
StudioHub Cable Requirements
- Must use shielded STP cable — UTP is not acceptable
- Cat5e STP or Cat6 STP (S/FTP preferred)
- T568B color code on both ends
- Max analog audio run: 300 ft (90 m)
- AES/EBU digital: shorter runs recommended (100–150 ft ideal)
- Standard 110-block or keystone patch panels — punch to T568B
- Use shielded patch panels and shielded patch cables
- Shield must be continuous throughout the run and bonded inside adapters
StudioHub+ Pinout (T568B)
| Pin | Pair Color | Signal | Function |
|---|---|---|---|
| 1 | Wht/Org | L AES+ | Left Ch. Positive / AES+EBU Positive |
| 2 | Org/Wht | L AES− | Left Ch. Negative / AES+EBU Negative |
| 3 | Wht/Grn | R+ | Right Channel Positive |
| 4 | Blu/Wht | GND | Signal Ground (bonded to cable shield) |
| 5 | Wht/Blu | NC | Not Connected — spare |
| 6 | Grn/Wht | R− | Right Channel Negative |
| 7 | Wht/Brn | −15V DC | Negative DC Power (StudioHub powered devices only) |
| 8 | Brn/Wht | +15V DC | Positive DC Power (StudioHub powered devices only) |
Adapter Color Band Convention
StudioHub vs IT Networking Standards
| Property | IT Networking (TIA-568) | StudioHub / AngryAudio |
|---|---|---|
| Cable Type | Cat5e–Cat6A UTP or STP | Shielded STP only (required) |
| Pinout Standard | T568A or T568B | T568B only |
| Connector | RJ-45 (data) | RJ-45 (audio — not interchangeable) |
| Max Run | 100 m (328 ft) | 90 m (300 ft) analog; shorter for digital |
| Pins 7 & 8 | Brown pair — data | ±15V DC power for StudioHub hubs |
| Pin 4 | Blue pair — data | Signal ground (bonded to shield) |
| Patch Panels | Standard 110-block, T568B | Same — standard panels work fine |
| Connect to Switch? | Yes — this is the purpose | NEVER — audio only |
| Compatible Gear | Any Ethernet device | Axia/Telos, Wheatstone, Angry Audio gear |